Gas monitor with self test: Compur Statox 4120

No new units sold anymore. 

Compur Monitors does support all existing systems with spare parts, consumables and service now and in future!

 Central Unit
 ½ l9″-rack maximum of 4  Dimensions: 180 x 270 x 420mm (h X w X d)
 plug-in control panels
 19″-rack maximum of 9  Dimensions: 180 x 485 x 420 mm (h X w X d)
 plug-in control panels
 Certificate:  [E Ex ib] IIC
 Control Module
 Recorder output  0 – 1 V, 4 – 20 mA
 Alarms  dual-level, user adjustable
 Relays  alarm 1, alarm 2, system fault, max. 24 V/100 mA
 LED  alarm 1, alarm 2, system run, system fault
 Data display  LED bar graph
Sensor Head Measuring Ranges:  Ambient  rel.  Storage
 temperature  Humidity  temperature
 Carbon monoxide CO  0-150 ppm  -20 – +40°C  20-90%  -30 – +60°C
 Chlorine Cl2  0-10 ppm  -20 – +40°C  30-80%  -30 – +60°C
 Chlorine dioxide  0-0,5 ppm  -20 – +40°C  20-95%  -30 – +60°C
 Hydrogen cyanide HCN  0-50 ppm  -20 – +40°C  20-90%  -30 – +60°C
 Hydrogen sulfide H2S  0-100 ppm  -20 – +40°C  20-90%  -30 – +60°C
 Phosgene COCl2  0-1,5/0-15 ppm  -20 – +40°C  20-90%  -30 – +60°C
 Nitrogen dioxide  0-15 ppm  -20 – +40°C  20-90%  -30 – +60°C
 Sulfur dioxide  0-5 ppm  -20 – +40°C  20-90%  -30 – +60°C
Sensor Head Specifications
 Protection class  IP 53
 Certificate  E Ex ib IIC T6
 Dimensions  180 x 180 x 300 mm (h x w x l)
 Weight  1,9 kg
 Diagnostic Unit
 Certificate  E Ex ib IIC T6
 Dimensions  50 x 160 x 190 mm (H x B x L)
 Weight  330 g

Manuals

Manual Statox 4120

Approval Statox 4120 

The software-controlled continuous warning system for toxic gas measuring: Cl2, ClO2, CO, COCl2,
HCN, H2S, HCl, NO2, SO2

System reliability by automatic self check

The Statox system incorporates an automatic self checking routine every 24 hours. The system completely checks all components including the sensor. The sensor is dynamically tested via an internally generated gas which assures that its´ response and recovery meet acceptable performance specifications. If a fault is detected in any of the components, it immediately notifies the control unit. The test can be initiated manually either from the control panel or the remote sensor head.