Statox 501S

This product has been further developed and is unfortunately no longer available. You can find the successor here: Statox 506

However, spare parts are still available.

Technical Data Measure Head
Sensor head: Statox 501S
Measuring principle: electrochemical
Operation temperature: -20 – +50°C
Humidity: 20 – 95 % r.H., not condensing
Pressure: 900 – 1100 hPa
Power supply: 24 VDC
Connections: 3- or 5- Wire
Output: 4 – 20 mA
Dimensions (HxWxD): 125 x 125 x 85 mm
Weight: 470 g
Housing material: ABS chrome plated
Ingress protection EN 60529: IP54
ATEX marking: II 2 G EEx ib IIC T5
Max. wire length: up to 2400 m, assembly in zone N
up to 570 m with Repeater, assembly in zone 1
Technical Data – Sensors
Sensor
Measure Range Working temperature Relative humidity
Chlorine Cl2 0 – 3 / 5 ppm -20 – +50 °C 20 – 95 %
Carbon monoxide CO 0 – 100 / 300 ppm -20 – +50 °C 20 – 90 %
Phosgene COCl2 0 – 0,3 / 1,0 / 15/ 100 ppm -20 – +50 °C 20 – 95 %
Hydrogen H2 0 – 150 / 300 / 1000 ppm -20 – +50 °C 20 – 90 %
Hydrogen sulphide H2S 0 – 100 ppm -20 – +50 °C 20 – 95 %
Hydrogen chloride HCl 0 – 50 ppm -20 – +50 °C 20 – 95 %
Hydrogen cyanide HCN 0 – 20 / 30 / 100 ppm -20 – +50 °C 20 – 95 %
Hydrogen fluoride HF 0 – 10 ppm -20 – +50 °C 20 – 95 %
Hydrazine N2H4 0 – 1,0 ppm -20 – +50 °C 20 – 95 %
Ammonia NH3 0 – 150 ppm -20 – +50 °C 15 – 95 %
Nitrogen dioxide NO2 0 – 10 / 50 ppm -20 – +50 °C 20 – 95 %
Oxygen O2 2 – 35 % -20 – +50 °C 20 – 95 %
Ozone O3 0 – 1,0 ppm -20 – +50 °C 20 – 90 %

Manuals

Statox 501S

Brochures

Statox 501S

Compatible Control Module

Statox 503